Single Core Cables
  Heat Resistant Single Core Cables
  Flex Cables
  Heat Resistant Flex Cables
  Halogen Free Cables
  230/400-300/500-450/750 V Cables
  0,6/1 KV Power Cables
  Welding Cables
  Special Rubber Cables
  Armoured Cables
 
 

 

Code: N2XH CU/XLPE/HFFR/XL HFFR

CU: IEC 60228 CLASS 1 & 2

U: Solid Conductor

R: Stranded Conductor

 

Standarts

VDE 0276

 

Technical Data

Max operating temperature: 90 0

Short circuit temperature: 250 0C ( max. 5 sn. )

Rated Voltage : 0,6 / 1Kv

 

Application

Used in internal and external places where human population is high and safety regulations must be taken against fire. They do not conduct flame during fire, do not create high smoke density, also do not create corrosive ambient.

 

Construction:

1- Solid or stranded  copper conductor

2- XLPE HFFR insulation

3- HFFR filter

4- Improved flame retardant XL HFFR sheath

 

 

 

 

BOYUT VE AĞIRLIKLAR

( DIMENSIONS AND WEIGHTS )

ELEKTRİKSEL ÖZELLİKLER

(ELECTRICAL PROPERTIES)

Tip

Type

Nominal Kesit

Nominal cross-section

Dış Çap (Yaklaşık)

Overall Diameter (approx.)

Net Ağırlık (yaklaşık)

Net wieght (apprx.)

İletken DC Direnci 20 0C'de max.

DC Condusctor Resistance at 20 0C

Akım Taşıma Kapasitesi

Current Carrying Capacity

Havada 30 0C'de

In Air at 30 0C

 

 

mm2

mm

kg/km

ohm/km

A

           
N2XH
1x4 6,8 72 4,61 55
1x6 7,4 95 3,08 70
1x10 8,4 140 1,83 95
1x16 9,5 200 1,15 126
1x25 10,6 290 0,727 170
1x35 12 390 0,524 210
1x50 13 500 0,387 255
1x70 15 720 0,268 325
1x95 17 970 0,193 399
1x120 19 1210 0,153 466
1x150 20 1500 0,124 536
1x185 23 1900 0,0991 621
1x240 26 2400 0,0754 743
2x1,5 9,7 130 12,1 29
2x2,5 10,6 162 7,41 138
2x4 11,5 205 4,61 50
2x6 12,5 260 3,08 64
2x10 14 370 1,83 87
3x1,5 10,5 145 12,1 29
3x2,5 11 185 7,41 38
3x4 12 245 4,61 50
3x6 13 315 3,08 64
3x10 15 460 1,83 87